Fire wardens in Germany (Brandschutzhelfer) are employees the employer has named to fight fires in their early stage. The technical rule ASR A2.2 gives 5% of the workforce as the usual figure. Refresher training has no legal deadline: for normal fire risk, ASR A2.2 says 2 to 5 years has worked in practice, and the risk assessment sets the interval.
This post shows where these numbers come from, how to calculate the headcount for your site, and when you need more wardens or shorter intervals. It ends with a simple record template. If you run a site in Germany from abroad, this is the part of German law your local team will be asked about.
Who has to appoint fire wardens
The duty is statutory. Section 10(2) of the German Occupational Safety and Health Act (ArbSchG) requires the employer to name employees who take on firefighting tasks. Their number, training and equipment must be in reasonable proportion to the headcount and to the specific hazards. The works council must be consulted before anyone is appointed.
Small firms have a shortcut. Under Section 10, the employer may do the job personally, as long as they have the training and equipment. The detail sits in the technical rule ASR A2.2 "Measures against fires" (BAuA, May 2018 edition, last amended 2025). An employer who follows it can assume the requirements of the Workplace Ordinance are met.
How many fire wardens: the 5% rule
Point 7.3 of ASR A2.2 says the number follows from the risk assessment, and a share of 5% of employees is usually enough. Treat it as a starting point, not a cap. Shift work and absences for training, holidays or illness must be counted.
A worked example with assumed numbers: a plant has 180 employees across three shifts of 60. 5% of 180 is 9. Spread evenly, that gives three wardens per shift. If one is on holiday, two are left. That is why many sites calculate per shift rather than per total headcount, and add a reserve.
Very small teams don't divide neatly. 5% of 12 employees is 0.6. Zero wardens would hardly be a "sufficient number" under the rule, so round up.
When 5% is not enough
ASR A2.2 itself lists the situations where a larger number may be needed:
| Situation in ASR A2.2 | What it means in practice |
|---|---|
| higher fire risk | stores of flammable goods, workshops, paint areas |
| many people present | sales floors, event rooms, canteens |
| people with limited mobility | care homes, nurseries, accessible workplaces |
| large premises | sprawling halls, several buildings on one site |
| lighter extinguishers with only 2 LE (point 5.2) | only allowed if, among other things, the number of wardens is doubled |
The last row is easy to miss. If you want lighter extinguishers with fewer than 6 extinguishing units (LE) to count towards the basic equipment under normal fire risk, ASR A2.2 requires, among other conditions, that you double the number of fire wardens. In the rule's own example of a nursery, every employee is trained.
Construction sites follow their own rule (point 8). Anyone who welds, flame-cuts, uses an angle grinder or solders must personally be trained in theory and practice to use an extinguisher. The 5% calculation does not apply there.
How often to refresh the training
There is no legal deadline. ASR A2.2 only contains a note: where the fire risk is normal, repeating the instruction with an exercise every 2 to 5 years has proven itself. The employer sets the interval based on the risk assessment.
Where you land in that range depends on your site. Shorter intervals make sense if the building, stored goods or firefighting equipment have changed, if staff turnover is high, or if an inspection showed wardens no longer know their tasks. Five years fits a stable office with normal fire risk better.
Keep this apart from the annual duty. Under point 7.2 of ASR A2.2, all employees must be briefed on fire safety measures before they start, when their duties change, and at least once a year after that. Fire wardens are not exempt. Our overview of German safety instruction duties (in German) lists the other annual briefings, and the post when to repeat safety instruction in Germany explains the logic behind them.
What the training must cover
Point 7.3(4) and (5) of ASR A2.2 set the content. Fire wardens receive expert instruction on:
- the basics of fire prevention,
- the company's fire safety organisation,
- how firefighting equipment works,
- the dangers of fire,
- what to do when a fire breaks out.
Hands-on extinguisher exercises come on top. The rule is clear that they are part of the expert instruction, so a webinar alone won't do. Firefighting equipment here means more than portable extinguishers: ASR A2.2 includes wall hydrants. If your building has hose reels, include them in the exercise. For more detail, ASR A2.2 points in its bibliography to the DGUV guidance 205-023 "Brandschutzhelfer".
Keeping a record: a simple template
ASR A2.2 does not prescribe a form. During an inspection, or a real fire, you still need to show who is appointed and when they practised. A table with these columns is enough:
| Column | Example |
|---|---|
| Name | M. Weber |
| Area / shift | Hall 2, early shift |
| Appointed on | 3 Feb 2025 (works council consulted) |
| Theory instruction on | 10 Feb 2025 |
| Hands-on extinguisher exercise | 10 Feb 2025, powder and water extinguishers |
| Next refresher due | Feb 2028 (interval per risk assessment: 3 years) |
| Annual briefing | 14 Jan 2026 |
With this list you can see at a glance when a shift falls short because someone has left.
Where VR helps, and where it doesn't
The real extinguisher exercise stays. Pulling the pin, feeling the weight and aiming the jet at the base of the fire are learned with the device in hand. But up to five years can pass between refreshers, and that is where knowledge fades.
That gap is where VR fits. In Fire Extinguisher Basic Training, employees practise recognising the fire class and picking the right extinguisher as often as they like, with no agent used up. Fire Hose Reel covers the second type of equipment named in ASR A2.2, and warehouses can use Warehouse Fire Marshal Training. New wardens can start practising before their next course. For a side-by-side look, read fire extinguisher training: classroom vs VR.
Fire wardens often help with evacuation too, so see how often fire drills are required. All trainings are in the VR training catalog.